FPI FIREPLACE PRODUCTS INTERNATIONAL LTD. 6988 Venture St., Delta, BC Canada, V4G 1H4918-156bMODELS: G36D-NG Natural Gas G36D-LP Propane01/04
UltraGlow G36D Zero Clearance Direct Vent Gas Fireplace10INSTALLATIONEXTERIOR VENT TERMINATION LOCATIONS.BBBBACVVVVVVVAAVFixedFixedOpenableClosedClose
UltraGlow G36D Zero Clearance Direct Vent Gas Fireplace 11VENTINGUltraGlow Direct Vent System (Flex)Horizontal Terminations OnlyThese venting systems
UltraGlow G36D Zero Clearance Direct Vent Gas Fireplace12INSTALLATIONRIGID PIPE VENTING COMPONENTS LISTAll Simpson Dura-Vent components are available
UltraGlow G36D Zero Clearance Direct Vent Gas Fireplace 13Rigid Pipe Adaptor(Part# 510-994)Pipe LengthVerticalTerminalStorm Collar(Part # 953)Flashing
UltraGlow G36D Zero Clearance Direct Vent Gas Fireplace14RIGID PIPE VENTING ARRANGEMENTS - HORIZONTAL TERMINATIONSULTRAGLOW DIRECT VENT SYSTEM (FLEX)
UltraGlow G36D Zero Clearance Direct Vent Gas Fireplace 15INSTALLATIONRIGID PIPE VENTING ARRANGEMENTS - HORIZONTAL TERMINATIONSULTRAGLOW DIRECT VENT S
UltraGlow G36D Zero Clearance Direct Vent Gas Fireplace16RIDID PIPE VENTING ARRANGEMENTS - VERTICAL TERMINATIONS(Propane & Natural Gas)The G36D is
UltraGlow G36D Zero Clearance Direct Vent Gas Fireplace 17INSTALLATIONThe G36D is approved for a maximum 37 ft. (11.3m) straight vertical, with Rigid
UltraGlow G36D Zero Clearance Direct Vent Gas Fireplace18INSTALLATIONVERTICAL TERMINATIONWITH CO-LINEAR FLEX SYSTEMThis appliance is designed to be at
UltraGlow G36D Zero Clearance Direct Vent Gas Fireplace 19INSTALLATIONVenting Arrangements - Vertical Terminations with Co-linear Flex System for both
UltraGlow G36D Zero Clearance Direct Vent Gas Fireplace2To the New Owner:Congratulations! You are the owner of a state-of-the-art Gas Stove by FIREPL
UltraGlow G36D Zero Clearance Direct Vent Gas Fireplace20Diagram 46) The arrow on the vent cap should be pointing up. Insure that the 1-1/2" cle
UltraGlow G36D Zero Clearance Direct Vent Gas Fireplace 21INSTALLATIONDiagram 3Diagram 5Diagram 1Diagram 2Note: Apply sealant "Mill-Pac" t
UltraGlow G36D Zero Clearance Direct Vent Gas Fireplace224) Separate the 2 halves of the wall thimble and securely fasten the one with the tabs to th
UltraGlow G36D Zero Clearance Direct Vent Gas Fireplace 23INSTALLATIONGAS PIPE PRESSURE TESTINGThe appliance must be isolated from the gas supply pipi
UltraGlow G36D Zero Clearance Direct Vent Gas Fireplace24CONVERSION KIT FROM NATURAL GAS TO PROPANE MODEL #290-969 FOR G36D USING SIT 820 NOVA GAS VAL
UltraGlow G36D Zero Clearance Direct Vent Gas Fireplace 25INSTALLATION5) Position Log 02-53 across the cutouts in Logs 02-75 and 02-51 with the notc
UltraGlow G36D Zero Clearance Direct Vent Gas Fireplace26INSTALLATIONLog indentationPhoto shows rear grate tab. Log 02-51 was removed to show the posi
UltraGlow G36D Zero Clearance Direct Vent Gas Fireplace 2710) Place the embers on the front of the burner tray in the places shown on the photos below
UltraGlow G36D Zero Clearance Direct Vent Gas Fireplace28Diagram 3Use the hook to pull the spring out until you can put the hook into the slot on the
UltraGlow G36D Zero Clearance Direct Vent Gas Fireplace 29Thermostat Wire TableOption 3: WALL THERMOSTAT A wall thermostat may be installed if desired
UltraGlow G36D Zero Clearance Direct Vent Gas Fireplace 3TABLE OF CONTENTSOperating InstructionsOperating Instructions ...
UltraGlow G36D Zero Clearance Direct Vent Gas Fireplace30WIRING DIAGRAM This heater does not require a 120V A.C. supply for operation. In case of a po
UltraGlow G36D Zero Clearance Direct Vent Gas Fireplace 31120 Volt AC power is needed for the fan switch and blower. A three wire power cord is provi
UltraGlow G36D Zero Clearance Direct Vent Gas Fireplace32OPERATING INSTRUCTIONSOPERATING INSTRUCTIONS1) Read and understand these instructions before
UltraGlow G36D Zero Clearance Direct Vent Gas Fireplace 33MAINTENANCE INSTRUCTIONS1) Always turn off the gas valve before cleaning. For relighting, r
UltraGlow G36D Zero Clearance Direct Vent Gas Fireplace34MAINTENANCE4) Make a periodic check of burner for proper position and condition. Visually c
UltraGlow G36D Zero Clearance Direct Vent Gas Fireplace 3513) Undo the pilot tube from the valve with a 7/16" wrench.14) Undo the quick drop out
UltraGlow G36D Zero Clearance Direct Vent Gas Fireplace36PARTS LISTG36D MAIN ASSEMBLY Part # Description Part #
UltraGlow G36D Zero Clearance Direct Vent Gas Fireplace 37G36D BURNER ASSEMBLY & LOG SET Part # Description 52) 910-190 Piezo Ignitor &
UltraGlow G36D Zero Clearance Direct Vent Gas Fireplace38PARTS LISTG36D FLUSH FRONT ASSEMBLY Part # Description131) 510-934 Flush Gl
UltraGlow G36D Zero Clearance Direct Vent Gas Fireplace 39WARRANTYUltraGlow products, are designed with reliability and simplicity in mind. In additio
UltraGlow G36D Zero Clearance Direct Vent Gas Fireplace4This is a copy of the label that accompanies each G36D Zero Clearance Direct Vent Gas Fireplac
Installer: Please complete the following informationDealer Name & Address: _______________________________________________________________________
UltraGlow G36D Zero Clearance Direct Vent Gas Fireplace 5INSTALLATION CHECKLIST1) Locate appliance a) Room location, page 6 b) Clearances to Comb
UltraGlow G36D Zero Clearance Direct Vent Gas Fireplace6INSTALLATIONDiagram 1This includes:1) Clocking the appliance to ensure the correct fi ring rat
UltraGlow G36D Zero Clearance Direct Vent Gas Fireplace 7MANTEL LEG CLEARANCESCombustible mantel leg clearances as per diagram below:FRAMING AND FINIS
UltraGlow G36D Zero Clearance Direct Vent Gas Fireplace8INSTALLATIONCOMBUSTIBLE MANTELSBecause of the extreme heat this fi replace emits, the mantel cl
UltraGlow G36D Zero Clearance Direct Vent Gas Fireplace 9"C" Screw Position:For a facing material depth of 1-1/4" (32mm), the top facin